Partner Manufacturers - Product Information

Xceedium XIO-XP8DPST20 xCONTROL POWER power control 8 - dual side static transfer 20A 110V


Description:
Xceedium’s xCONTROL POWER provides a remote power control solution that allows administrators to turn on, turn off, or reboot any device that is connected to it, from a remote location or local terminal.

The unit contains 8 individual relay controlled AC power receptacles that are controlled by sending a short character string (command) to the ethernet or RS-232 control port on the host module.

If power is lost to the unit due to an outage, it retains the last known state of each receptacle so that when power returns, only the appropriate receptacles power back on.

When used in conjunction with the SSL-UAG+, administrators can achieve secure web-based access and centralized management and control of any of our xCONTROL POWER units, anywhere, anytime.

Supports commands for both receptacle control and status, including: on, off, config, reboot and status. Provides a response to a command indicating that the command was acknowledged and completed.

Access
xCONTROL POWER is accessible and/or controllable via Ethernet or Serial port.

Advanced Applications
xCONTROL POWER series include many models that satisfy customers’ requirement. For example, in most cases, the power output and power cords can be customized to meet the requirements of the plug-in devices as well as the cord can be switched from NEMA-15 to Twisted Lock type for under-raised-floor installations. Additionally, for enterprise-class redundancy, xCONTROL POWER series include models with Redundant Switching, Static Transferring, and Three-Phase Capabilities.

Control
xCONTROL POWER supports commands for both receptacle control, and status. These commands include: on, off, config, reboot and status. The unit provides a response to a command indicating that the command was acknowledged and completed. In the event of a power failure to the xCONTROL POWER, the unit retains the most current operational status for each outlet in non-volatile memory. When the xCONTROL POWER regains power, it restores each outlet to those status settings. For example: If Outlets 1 and 2 are ON, and the remaining outlets are OFF when a power loss occurs, when AC power is restored, Outlets 1 and 2 are placed in the ON position. The power-up routine to each receptacle is performed sequentially to minimize power surges.

Features:
Manage Power to the Receptacle Level (On, Off, Reboot)

  • Reboot Unresponsive Equipment

  • Turn Off Unused Receptacles

  • Log and Maintain Receptacle Connectivity

  • Monitor and Control Power Using Xceedium’s SSL-UAG+ or Existing NMS Software

  • Standard Power Distribution for Single/Dual Corded Applications Monitor Power to Circuit Level with True RMS: Current, Voltage, Watts, VA

  • Receive Alarms Based on Preset Thresholds

  • Audit Circuit Prior to Plugging in More Equipment

  • Plan Cooling Requirements by Using Watt Readings

  • Audible and LED Alarm Warnings Monitor Internal Temperature

  • Receive Alarms Based on Preset Thresholds

  • Eliminate Equipment Failure due to Excessive Heat Well-Suited for Low-Density Applications

  • 8 Controllable Receptacles

  • Single-Cord Power Input

  • Rack-Mount Unit
  • Specification:
    LOGICAL NAME
    Outlet 1 for Receptacle 1,...Outlet 8 for Receptacle 8. Programmable Up to 10 Characters per Receptacle

    POWER RECEPTACLES*
    (8) NEMA 5-15 Receptacles

    CIRCUIT BREAKER*
    115V, 15 Amp

    CORD LENGTH*
    6 Ft.

    SECURITY
    Password Protection (DEFAULT)

    DIMENSIONS
    16.73"w x 7.168"d x 1.72"h

    INDICATORS
    Power Indicator LED, Receptacle On/Off Indicator LEDs

    ENVIRONMENTAL CHARACTERISTICS

    OPERATING TEMPERATURE
    Range is 0 to 40 Degrees Celsius

    STORAGE TEMPERATURE
    Range is -40 to 80 Degrees Celsius

    HUMIDITY
    5 to 95% RH

    MOUNTING
    Rack-Mount or Desktop

    ACCESSORIES
    Speak with an Xceedium Sales Representative to determine the correct parts and cables needed for your solution.

    WARRANTY
    One Year Parts and Labor


    *Additional Configurations Available Depending on Regional Requirements, Inventory and Volume of Order