Partner Manufacturers - Product Information

KWX-ATS16A8x2-H1C20 KWX 19" PDU 2 x Inputs C20 16A to 8xC13 + 2xC19 Rack mount Automatic Transfer Switch (8-12 ms Switching ) (KWX ATS). With bar unit remote monitoring KWX-N1 Range


KWX-ATSH2

Description:
KWX Rack mount Automatic Transfer Switch (KWX ATS).
2x 16A C20 Inputs to 10x Outlets 8xC13, 2xC19

Provides Total Current Monitoring and Outlets power usage, delivers consistent power, to single-corded equipment. The KWX ATS has
dual input power cords supplying power to the connected load. In the event where the primary power source becomes unavailable, the KWX ATS will flawlessly source power from the secondary source
without interrupting critical loads. The KWX ATS has built-in network connectivity, which allows for remote management via Web, SNMP or Telnet/SSH interfaces, and provides sensors recognition,
ability to cascade up to 2 units, power factor recognition, 8 x lockable IEC-C13 and 2x C19, 2 x C20 input. Dry connection
Optional: temperature and humidity, smoke alarm, water logging alarm, infrared alarm, and door open alarm.
Monitor: monitor the total current, monitor the total kWh, and monitor the input voltage, monitor environment temperature, monitor environment humidity, monitor environment smoke, monitor
water logging, infrared monitoring, and door open monitoring.
Alarm settings: total current over the limit, on the temperature limit, on the humidity limit, smoke alarm, and water logging alarm, infrared enters alarm, door open alarm.

Features:
-2 x 16Amp IEC C20 Input to 8x Locking C13 Outlets 10 Amp + 2 x C19 16 Amp

- High Speed - Fast switching A-B Source 8~12 ms

-Surge Protected

- Alarm Settings

- Sensor Port for enviromental sensors ( optional extra )

- RS232 Port

Locking Sockets view

Specification:
Item Description
Product series KWX-N-ATS-2
Product Size W x D x H= 19“ x 248 x 44.45 mm
Mounting
length 465 mm
Case color Black

Output Socket types:
Lockable IEC 320 C13 10 A + IEC 320 C19 16 A

Two Inputs:
A&B IEC320 C20 16A

Input/output voltage Total load current Power supply A or B line operating state

Function - Automatic switch over power A and power B

Overload alarm When over the 16A threshold both the ATS alarm and the LED display will be activated.

Switching time (From "A" to "B" line): 8 ms ≤ 12 ms


Function Illustration Parameter Note
Working voltage Normal working AC90~250V
Input/output current Max input/output current 16A
10A/16A
Working band Under normal working 47~60Hz
Access
port
Net port Via WAN or LAN monitor access 10/100Mb
Adaptive Networking
Serial port Via Serial port monitor access RS485 port
Sensor port Sensors access RS485 port
Access way
HTTP/
HTTPS Web browser access Adapt IE、Firefox inner core browser, support
SSL;
TELNET Simple command lines access /
SSH Encryption command lines access Support SSHV2 version
SNMP Support SNMP for centralized monitor Adapt SNMP v1、V2

Operation system compatibility Support various operation system Windows/winsta/win7/linux etc.
Secondary development
Used for system integrate Opening protocol TELNET、SSH
RS485 Customized protocol
Software upgrade
Manage software load Support manage software upgrade
Software on circuit Support software upgrade on the circuit of
hardware
Monitor
Inspect the fuse status of each ports Monitor when fuse break or outlets can’t be
controlled Optional
Monitor the input voltage
Resolution:1V
Accuracy: ±1%+1 digit
Meter range: 90~350V
Monitor the total current
Resolution: 0.1A
Accuracy: ±1%+1 digit
Meter range: 0.1~40A
Monitor each sockets current
Resolution: 0.1A
Accuracy: ±1%+1 digit
Meter range: 0.1~20A
Monitor the total kwh Resolution: 0.1KW·H
Accuracy: 1 grade
Monitor Environment Temperature
Resolution: 1℃
Accuracy: ±1%+1 digit
Meter range: -30~100℃
Optional
Monitor Environment Humidity
Resolution: 1%
Accuracy: ±1%+1 digit
Meter range: 01~99%
Optional
Monitor Environment Smoke Max: 25 ㎡ available Optional
Monitor water logging Water logging or drop monitor Optional
Infrared monitoring The max monitor distance: 16m Optional
Door open monitor Min. 5mm open distance available Optional
Surge protection failure monitor PDU still normal working when failure Optional
Alarm limit setting
Total current limit
Auto identify limit rationality
Each ports current limit
Temperature limit
Humidity limit
Outlets alarm
Each fuse failure alarm
KWX-S/KWX-N series local alarm ways: PDU
buzzer alarm, sound and light alarm, Dry
connect;
KWX-N series remote alarm: E-mail, SMS,
SNMP TRAP, WEB page notice, TELNET/SSH
notice
Optional
Each outlets current over limit alarm
Total current over limit alarm
Temperature over limit alarm Optional
Humidity over limit alarm Optional
Smoke Alarm Optional
Water logging alarm Optional
Infrared enter alarm
KWX-N series remote alarm: E-mail, SMS,
SNMP TRAP, WEB page notice, TELNET/SSH
notice
Optional
Door open alarm Optional
Surge protection failure alarm Optional
Display, Indicate
Outlets indicators Each outlets with a indicator Optional
6 digital indicators Nixie tube show the current/voltage, inquiry
products information, Alarm information;
Manu button operation
Inquiry information Inquiry product information, Alarm information,
current etc.
On/off Alarm sound, Dry connect
Close/ open alarm sound and dry connect output,
Dry connect have normal open/off two choice,
passive, touch spot can connect 2A 250VAC

Protection
Surge protection
Difference mode:±2kV
Common mode :±2KV
flux: 3KA
The max discharge current: 5KA
Optional
Each way with fuse
Breaking capacity : 1500A;
Protect main line break, facility, power line
suffering, Fuse range: 0.1~16A
Optional
Circuit Breaker protection Breaking capacity : 6000A Optional
Recoverable overload protector Overload protection Optional
Log record Alarm log Alarm log circle, Inquiry, export, stock, delete
available
Management
User right limit Administrator, Normal user
Outlets grouping Make group over PDU self sockets limit
clock synchronization Regulate PDU system clock
Intelligent recognition
Outlets recognition Automatic read the sockets type and numbers
Sensors recognition Sensors port no need to be defined, Automatically
read the sensors type and numbers
Limit recognition When over limit, setting failure
The MAX output current and PDU power Help user to limit facilities connected number and
type
Power factor recognition
Help user to know the current consuming
apparatus
Sensors in 1 ~ 8pcs same or different sensors connect in one
PDU
Flexible sensor input, extend and choose,
Customized for new sensors Optional
Cascade chain
KWX-N with KWX-N Cascade
Directly connection via net cable;
Via HUB ,4 sets Cascade at most
KWX-N with KWX-S Cascade Directly connection via net cable, 2 sets Cascade
at most